Ventilation & smoke extraction enclosures

Advantages

  • No steel sheet ducts are required
  • Single shell construction
  • Dimensionally stable and resistant to moisture
  • Easy to cut to size, ex factory or on site
  • Lightweight shaped sections
  • Serviceable smooth surface, robust

Ventilation & smoke extraction enclosures

Fire protection requirements for ventilation ducts are directly related to their design function, the nature and behaviour of the fire and the construction materials that fuel the fire load. The fire resistance performance of the ventilation duct itself also plays a critically important role.

Ventilation ducts up to 120 minutes fire resistance

Sheet steel ducts from an independent manufacturer can be cladded with PROMATECT® fire protection boards or the duct can be fabricated entirely from PROMATECT® fire protection boards.

When existing steel sheet ducts are cladded, for example, with PROMATECT® fire protection boards it is necessary to satisfy additional fire protection requirements for change in use status.

Ventilation ducts are tested according to EN 1366-1 and classified according to EN 13501-3. The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. Promat solutions in both cases (with or without steel ducts) fulfil the requirements from both sides ‘(i ↔ o)’.

A more economical solution, however, is achieved by specifying and installing tested and proven PROMATECT® ventilation ducts from Promat, the world leader in professional fire science technologies.

Heat and smoke control ducts up to 120 minutes fire resistance

The smoke extraction lines are tested automatically with fire load from both sides. Basically two heat and smoke control ducts can be distinguished:

  • single compartment smoke control ducts, which can be used in one fire section only and are tested according to EN 1366-9 and classified according to EN 13501-4
  • multi compartment fire resistant smoke control ducts, which can be used in any number of fire sections and are tested according to EN 1366-8 and classified according to EN 13501-4

Promat offers solutions without steel ducts for both systems up to 120 minutes fabricated with PROMATECT® fire protection boards.